| Power rating | 120 W | 240 W | ||
|---|---|---|---|---|
| Output voltage | 24 V | 24 V | ||
| Efficiency | 3-phase, 400
VAC input *11 |
89% typ. | 89% typ. | |
| Input | Voltage range *1 | 3-phase, 380 to 480 VAC (allowable range: 320 to 576 VAC)
2-phase, 380 to 480 VAC (allowable range: 340 to 576 VAC) 450 to 600 VDC (allowable range: 450 to 810 VDC) *8 |
||
| Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||
| Current | 3-phase, 400
VAC input *11 |
0.38 A typ. | 0.69 A typ. | |
| Power factor | - | - | ||
| Leakage
current |
3-phase, 400
VAC input |
3.5 mA max./1.3 mA typ. | 3.5 mA max./1.4 mA typ. | |
| Inrush
current (for a cold start at 25°C) *2 |
3-phase, 400
VAC input |
28 A typ. | 29 A typ. | |
| Output | Rated output current | 5 A | 10 A | |
| Boost current | 6 A | 12 A | ||
| Voltage adjustment range *3 | 22.5 to 29.5 VDC (with V.ADJ) (guaranteed) | |||
| Ripple & Noise
voltage *4 |
3-phase, 400
VAC input *11 |
160 mV p-p max. at 20 MHz of
bandwidth |
190 mV p-p max. at 20 MHz of
bandwidth |
|
| Input variation influence *13 | 0.5% max. | |||
| Load variation influence *12 | 1.5% max. | |||
| Temperature
variation influence |
3-phase, 400
VAC input |
0.05%/°C max. | ||
| Start up time
*2 |
3-phase, 400
VAC input *11 |
700 ms typ. | 600 ms typ. | |
| Hold time *2 | 3-phase, 400
VAC input *11 |
30 ms typ. | 20 ms typ. | |
| Additional
functions |
Overload protection | Yes, automatic reset | Yes, automatic reset | |
| Overvoltage protection | Yes, 130% or higher of rated output voltage, power shut off (shut off the
input voltage and turn on the input again) *5 |
|||
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) | |||
| Parallel operation | Yes (Refer to Engineering Data) (For up to two Power Supplies) | |||
| Output indicator | Yes (LED: Green), lighting from 80% to 90% or more of rated voltage | |||
| Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals)
cutoff current 20 mA 2.5 kVAC for 1 min. (between all input terminals and PE terminal) cutoff current 20 mA 1.0 kVAC for 1 min. (between all output terminals and PE terminal) cutoff current 30 mA |
||
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE
terminal) at 500 VDC |
|||
| Envi-
ronment |
Ambient operating temperature | -40 to 70°C (However, only startup is guaranteed for between -40°C
to -25°C. (3-phase only)) (Derating is required according to the temperature.) (with no condensation or icing) |
||
| Storage temperature | -40 to 85°C (with no condensation or icing) | |||
| Ambient operating humidity | 0% to 95% (Storage humidity: 0% to 95%) | |||
| Vibration resistance | 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z
directions |
|||
| Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions | |||
| Reliability | MTBF | 135,000 hrs min. | ||
| Life expectancy *10 | 10 years min. | |||
| Con-
struction |
Weight | 700 g max. | 1,000 g max. | |
| Cooling fan | No | |||
| Degree of protection | IP20 by EN/IEC 60529 | |||
| Standards | Harmonic current emissions | Conforms to EN 61000-3-2 | ||
| EMI | Conducted
Emission |
Conforms to EN 61204-3 Class B EN 55011 Class B | ||
| Radiated
Emission |
Conforms to EN 61204-3 Class B EN 55011 Class B | |||
| EMS | Conforms to EN 61204-3 high severity levels | |||
| Approved Standards *6 | UL Listed: UL 508 *7
EN: EN 50178 Lloyd's standards *9 ANSI/ISA 12.12.01 *7 |
UL Listed: UL 508 *7
UL UR: UL 60950-1 (Recognition) cUR: CSA C22.2 No.60950-1 CSA: CSA C22.2 No.60950-1 EN: EN 50178, EN 60950-1 Lloyd's standards *9 ANSI/ISA 12.12.01 *7 |
||
| Conformed Standards | SELV (EN 50178),
PELV (EN 60204-1, EN 50178) Safety of Power Transformers (EN 61558-2-16) EN 50274 for Terminal parts |
SELV (EN 60950-1/EN 50178/
UL 60950-1) PELV (EN 60204-1, EN 50178) Safety of Power Transformers (EN 61558-2-16) EN 50274 for Terminal parts |
||
| SEMI | Conforms to F47-0706 (3-phase, 380 to 480 VAC input) | |||