General-purpose Relay
Image
| Coil ratings |
200 VAC 5.5 mA (50 Hz) / 200 VAC 4.5 mA (60 Hz) / 220 VAC 5.3 mA (60 Hz) |
|---|---|
| Operating indicator |
Not equipped |
| Coil surge killer |
Not equipped |
| Contact type |
SPDT |
| Contact method |
Single |
| Contact material |
Contact body: Ag alloy Contact finish: Nothing |
| Contact rated load |
250 V AC10 A (Resistive load) 250 V AC7.5 A (Inductive load (cos φ= 0.4, L/R = 7 ms)) 30 VDC 10 A (Resistive load) 30 VDC 5 A (Inductive load (cos φ= 0.4, L/R = 7 ms)) |
| Maximum switching current |
AC: 10 A DC: 10 A |
| Terminal structure |
Plug-in terminal |
As of September 9, 2016
| Product classification | Monostable relays Standard type |
|---|---|
| Coil ratings | 200 VAC 5.5 mA (50 Hz) / 200 VAC 4.5 mA (60 Hz) / 220 VAC 5.3 mA (60 Hz) |
| Coil resistance | 20200 Ω |
| Operate voltage (Set voltage) | 80 % max. |
| Release voltage (Reset voltage) | 30 % min. |
| Max. voltage | 110 % (of rated voltage) |
| Power consumption | 0.9 VA max. (60 Hz) |
| Operating indicator | Not equipped |
| Coil surge killer | Not equipped |
| Contact type | SPDT |
| Contact method | Single |
| Contact material | Contact body: Ag alloy Contact finish: Nothing |
| Contact rated load | 250 V AC10 A (Resistive load) 250 V AC7.5 A (Inductive load (cos φ= 0.4, L/R = 7 ms)) 30 VDC 10 A (Resistive load) 30 VDC 5 A (Inductive load (cos φ= 0.4, L/R = 7 ms)) |
| Maximum switching voltage | 440 VAC (Resistive load) 125 VDC (Resistive load) |
| Maximum switching current | AC: 10 A DC: 10 A |
| Maximum switching power | AC: 2500 VA (Resistive load) AC: 1875 VA (Inductive load (cos φ= 0.4, L/R = 7 ms)) DC: 300 W (Resistive load) DC: 150 W (Inductive load (cos φ= 0.4, L/R = 7 ms)) |
| Failure rate | 100 mA at 5 VDC (failure level: P Reference value) |
| Ambient temperature (Operating) | -40 to 70 ℃ (with no icing or condensation) |
| Ambient_humidity (Operating) | 5 to 85%RH (with no icing or condensation) |
| Contact resistance | 30 mΩ max., Measuring the voltage drop across the contacts by applying test voltage/current as 5 VDC 1 A |
| Operating time (set time) | 15 ms |
| Release time (Reset time) | 10 ms |
| Max.operating frequency (Mechanical) | 18000 |
| Max.operating frequency (Erectrical) | 1800 opn./h |
| Insulation resistance | Between coil and contacts: 1000 MΩ min. (at 500 VDC) Between contacts of same polarity: 1000 MΩ min. (at 500 VDC) |
| Dielectric strength | Between coil and contacts: 5000 V (50/60 Hz 1 min) Between contacts of same polarity: 1000 V (50/60 Hz 1 min) |
| Vibration resistance (Destruction) | 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
| Vibration resistance (Malfunction) | 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
| Shock resistance (Destruction) | 1000 m/s**2 |
| Shock resistance (Malfunction) | 200 m/s**2 when energized 100 m/s**2 when no energized |
| Endurance (Mechanical) | 10,000,000 operations min. |
| Endurance (Electrical) | 100,000 operations min. |
| Protective structure | Closed type (cover) |
| Terminal structure | Plug-in terminal |
| Weight | Approx.20 g |
As of September 9, 2016
Series
about this Product